SG(B)13 & SC(B)13 Dry‑Type Distribution Transformers
|
Meaning of Model Number |
S |
G/C |
(B) |
13 |
- |
□ |
/ |
□ |
|
|
Three-phase |
G: Non-encapsulated type (Class H) |
Low voltage foil wound coils can be used |
Performance level code |
|
Rated capacity kVA |
|
Voltage class kV |
1. Two structural options adapting different site conditions
SG(B)13 open‑type H‑class design realizes excellent heat dissipation for well‑ventilated space. SC(B)13 vacuum epoxy cast winding delivers high mechanical robustness, dust‑resistance and moisture‑resistance for demanding indoor environment. Loss performance is improved versus level‑12 series for lower operating cost.
2. High mechanical strength & superior short‑circuit withstand capacity
Optimized winding structure together with premium silicon‑steel core enhances anti‑short‑circuit performance, effectively resist mechanical impact under fault conditions and extend service life. Low partial discharge ensures stable long‑time running.
3. Complete intelligent thermal protection system
Multi‑channel winding temperature detector matches dedicated controller. It cyclically displays real‑time temperature of three‑phase windings, automatically switches cooling fans, triggers overtemperature alarm and tripping signal to protect transformer safety.
4. Overload capacity & wide environmental adaptability
With forced‑air cooling, short‑term overload operation is achievable. Good moisture‑resistant property guarantees stable running in high‑humidity environment. Working ambient temperature:‑25 ℃ ~ 45 ℃.
5. Safe, eco‑friendly and maintenance‑free
Oil‑free structure eliminates fire risk and oil leakage hazard. Pollution‑free, fire‑resistant and explosion‑proof, requiring almost no routine maintenance, ideal for indoor substations with strict fire‑protection rules.
6. Flexible configurable options
Copper windings standard; aluminum windings available. Support off‑circuit tap‑changer, anti‑condensation heater and stainless steel enclosure. Compact dimension saves installation footprint and project cost.
|
Model |
Rated capacity (kVA) |
Vector group |
Voltage combination(kV) |
No-load loss (W) |
Load loss(W)120℃ (F) |
No-load current (%) |
Impedance voltage (%) |
||
|
High voltage |
Tapping range |
Low voltage |
|||||||
|
SC(B)13-30 |
30 |
Yyn0或Dyn11 |
10 6.3 6 |
±5% ±2x2.5%或 3x2.5%/-1x2.5% |
0.4 |
135 |
640 |
2 |
4 |
|
SC(B)13-50 |
50 |
195 |
900 |
2 |
|||||
|
SC(B)13-80 |
80 |
265 |
1240 |
1.5 |
|||||
|
SC(B)13-100 |
100 |
290 |
1410 |
1.5 |
|||||
|
SC(B)13-125 |
125 |
340 |
1660 |
1.3 |
|||||
|
SC(B)13-160 |
160 |
385 |
1910 |
1.3 |
|||||
|
SC(B)13-200 |
200 |
445 |
2270 |
1.1 |
|||||
|
SC(B)13-250 |
250 |
515 |
2480 |
1.1 |
|||||
|
SC(B)13-315 |
315 |
635 |
3120 |
1 |
|||||
|
SC(B)13-400 |
400 |
705 |
3590 |
1 |
|||||
|
SC(B)13-500 |
500 |
835 |
4390 |
1 |
|||||
|
SC(B)13-630 |
630 |
965 |
5290 |
0.85 |
|||||
|
SC(B)13-630 |
630 |
935 |
5360 |
0.85 |
6 |
||||
|
SC(B)13-800 |
800 |
1090 |
6260 |
0.85 |
|||||
|
SC(B)13-1000 |
1000 |
1270 |
7310 |
0.85 |
|||||
|
SC(B)13-1250 |
1250 |
1500 |
8720 |
0.85 |
|||||
|
SC(B)13-1600 |
1600 |
1760 |
10500 |
0.85 |
|||||
|
SC(B)13-2000 |
2000 |
2190 |
13000 |
0.7 |
|||||
|
SC(B)13-2500 |
2500 |
2590 |
15400 |
0.7 |
|||||
SG(B)13 and SC(B)13 are level‑13 high‑efficiency dry‑type transformers with reduced no‑load & load losses compared with level‑12 series.
‑ SG(B)13: Open non‑encapsulated H‑class insulation structure, outstanding heat dissipation, cost‑effective choice for well‑ventilated indoor sites.
‑ SC(B)13: Epoxy resin vacuum cast winding, superior mechanical strength, dust‑proof and moisture‑proof performance, fit for dusty or high‑humidity indoor working conditions.
Both series adopt high‑grade silicon‑steel core, featuring strong short‑circuit withstand capability, low noise and remarkable energy‑saving effect. Equipped with complete intelligent temperature controller: cyclic three‑phase winding temperature display, automatic cooling fan start‑stop, overtemperature alarm and tripping function. Forced‑air cooling enables temporary overload operation. Fire‑safe, oil‑free and maintenance‑free. Capacity:30‑2500 kVA, max voltage 24 kV.