Products
Products
HomeProductsHigh-Voltage Switchgear SeriesGCS Low‑Voltage Draw‑out Type Switch Cabinet, Motor Control Center MCC Panel

GCS Low‑Voltage Draw‑out Type Switch Cabinet, Motor Control Center MCC Panel

Features :
Draw‑out modular low‑voltage switchgear, rated main‑circuit current up to 4000A
Rated working voltage: AC 380(400)V / 660V, frequency 50/60Hz
Horizontal busbar rated current ≤4000A, vertical busbar(MCC) 1000A
Short‑time withstand current: 50kA / 80kA optional
Function‑compartment isolated design, safe maintenance without power‑off for single drawer
Fully‑assembled / partial‑welded two frame‑installation options
Perfect for automated industrial workshop & computer‑interface‑required projects
Protection grade IP30 / IP40 available
Comply with IEC439‑1, GB7251, ZBK360001 international standards
Easy expansion, convenient maintenance, high system reliability
Product Overview:

GCS low‑voltage draw‑out switch cabinet is a modular motor‑control‑center switchgear, widely used in power distribution systems of power plants, petroleum, chemical, metallurgy, textile, high‑rise buildings and other industries.

It is especially suitable for large‑scale power‑plants and petro‑chemical projects with high automation requirements and computer‑interface access. Working at AC 50/60Hz, rated voltage 380(400)V / 660V, rated current up to 4000A, it undertakes power distribution, motor centralized control and reactive‑power compensation tasks in low‑voltage power supply networks.

This equipment strictly conforms to standards: IEC439‑1, GB7251, ZBK360001.

Meaning of Model Number
Code G C S Main‑circuit scheme No. Auxiliary‑circuit scheme No.
Explanation Low‑voltage enclosed switchgear Draw‑out type Motor‑control‑center cabinet Separator Main‑circuit configuration number Separator Auxiliary‑circuit configuration number
Service Conditions

‑ Ambient temperature: ‑5℃ ~ 40℃, average temperature within 24h ≤ 35℃
‑ Installation altitude: ≤ 2000 m
‑ Relative humidity: ≤ 50% at 40℃; higher humidity allowed at lower temperature (condensation protection required)
‑ No severe vibration, impact, corrosive gas or conductive dust in installation environment
‑ Indoor installation only, avoid rain & snow erosion

Structural Features
  1. High‑strength 8MF profile frame The main frame is welded by 8MF open‑type section steel. Both sides are pre‑drilled mounting holes of 20 mm, 100 mm pitch and Φ9.2 mm, flexible for internal component installation.
  2. Two optional assembly forms Fully‑assembled structure; Partial‑frame & beam welding‑type structure, for customers to select according to site requirements.
  3. Independent isolated compartment design All functional areas are physically separated: drawer unit compartment, bus‑bar compartment, cable compartment. Each section operates relatively independently, greatly improving operation‑safety, preventing fault‑spread risk.
  4. Convenient hot‑swap maintenance Single drawer loop can be pulled‑out for inspection or replacement, without shutting‑down the whole cabinet, minimizing production downtime.
  5. Flexible expandability Modular drawer‑unit design, you can add, remove or modify motor & feeder loops later without reconstructing the main cabinet.
Main Technical Parameters
Item Parameter
Main‑circuit rated voltage AC 380(400)V, (660V)
Auxiliary‑circuit rated voltage AC 220V / 380(400)V; DC 110V / 220V
Rated frequency 50(60)Hz
Rated insulation voltage 660(1000)V
Horizontal busbar rated current ≤ 4000 A
Vertical busbar (MCC) rated current 1000 A
Busbar rated short‑time withstand current (1s) 50kA, 80kA
Busbar rated peak withstand current (0.1s) 105kA, 176kA
Power‑frequency withstand voltage‑Main circuit 2500 V / 1min
Power‑frequency withstand voltage‑Auxiliary circuit 1760 V / 1min
Bus‑bar wiring system 3‑phase 4‑wire(A,B,C,PEN); 3‑phase 5‑wire(A,B,C,PE,N)
Protection grade IP30, IP40