KYN28A‑12 Indoor Draw‑out Armored AC Metal‑Enclosed High‑Voltage Switchgear, 12kV
KYN28A‑12 indoor AC armored removable metal‑enclosed switchgear is suitable for three‑phase AC power systems with rated voltage of 12kV and rated frequency of 50Hz, for receiving and distributing electrical energy, as well as for controlling, protecting and monitoring circuits.
This product complies with the requirements of GB3906 "AC Metal‑enclosed Switchgear for Rated Voltages of 3.6kV to 40.5kV", GB/T11022 "Common Technical Requirements for High‑voltage Switchgear and Control Equipment", IEC60298 "AC Metal‑enclosed Switchgear and Controlgear for Rated Voltages Above 1kV and Up to 52kV", and DL/T404 "Technical Specification for Indoor AC High‑voltage Switchgear".
Full anti‑misoperation interlock functions are equipped: preventing moving‑cart operation under load, forbidding breaker closing while earthing switch is on, avoiding earthing‑switch closing on live circuits and blocking unauthorized access to live compartments. With compact layout, easy‑operation design and stable performance, it delivers high‑safety indoor power‑distribution.
| Meaning of Model Number | K | Y | N | 28 | ‑ | 12 | Z |
|---|---|---|---|---|---|---|---|
| Explanation | Armored metal‑clad cabinet | Removable / draw‑out type | Indoor installation | Design serial number | Separator | Rated voltage(kV) | Vacuum circuit‑breaker |
- Ambient air temperature: Max 40℃, Min ‑15℃
- Relative humidity: Daily average ≤95%, daily average water‑vapour pressure ≤2.2kPa; Monthly average ≤90%, monthly average water‑vapour pressure ≤1.8kPa
- Altitude: ≤1000m above sea‑level
- Earthquake intensity: ≤Grade 8
- Surrounding air: No obvious pollution by corrosive or flammable gas, water vapour etc.
- No violent vibration at installation site
- For operation environments exceeding GB3906 standard conditions, special technical solutions can be negotiated between our factory and buyers
| Item | Unit | Parameter |
|---|---|---|
| Rated Voltage | kV | 3.6, 7.2, 12 |
| Rated Frequency | Hz | 50 |
| Rated Current of Circuit Breaker | A | 630, 1250, 1600, 2000, 2500, 3150 |
| Rated Current of Switchgear | A | 630, 1250, 1600, 2000, 2500, 3150 |
| Rated Short‑time Withstand Current (4s) | kA | 20, 25, 31.5, 40 |
| Rated Peak Withstand Current | kA | 50, 63, 80, 100 |
| Rated Short‑circuit Breaking Current | kA | 20, 25, 31.5, 40 |
| Rated Short‑circuit Making Current (peak) | kA | 50, 63, 80, 100 |
| 1min Power‑frequency Withstand Voltage (phase‑to‑earth / between phases) | kV | 24, 32, 42 |
| 1min Power‑frequency Withstand Voltage (across isolating gap) | kV | 28, 32, 42 |
| Lightning‑impulse Withstand Voltage (phase‑to‑earth / between phases) | kV | 40, 60, 75 |
| Lightning‑impulse Withstand Voltage (across isolating gap) | kV | 46, 70, 85 |
| Protection Degree | Shell IP4X; Between compartments & when breaker‑compartment door open: IP2X |